Annunciations 7UT51X for LSA (DIN 19244 and according IEC 60870-5-103)
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
FNo. - Function number of annunciation
Op/Ft - Operation/Fault annunciation
C/CG: Coming/Coming and Going annunciation
V : Annunciation with Value
M : Measurand
LSA No.- Number of annunciation for former LSA (DIN 19244)
according to IEC 60870-5-103:
CA - Compatible Annunciation
GI - Annunciation for General Interrogation
BT - Binary Trace for fault recordings
Typ - Function type (p: according to the configured "Function type")
Inf - Information number
¿©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©©©©§©©©§©©©©©©©©©©©©©©©©¤
Ann.LSAIEC 60870-5-103
FNo. Meaning OpFtNo.CAGIBTTypInf
¨©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©©©ª©©ª©©ª©©ª©©©ª©©©
11>User defined annunciation 1 CG 50CAGIBT p 27
12>User defined annunciation 2 CG 56CAGIBT p 28
13>User defined annunciation 3 CG 57CAGIBT p 29
14>User defined annunciation 4 CG 58CAGIBT p 30
51Device operative / healthy CG 1 GI 135 81
52Any protection operative CG CAGI p 18
55Re-start of processor system C 193CAp4
56Initial start of processor system C 194CAp5
59Real time response to LSA C 192
60LED Reset C 30CAp19
61Logging and measuring functions blockedCG CAGI p 20
62Test mode CG CAGI p 21
63PC operation via system interface CG 135 83
95Parameters are being set CG 97CAGI p 22
96Parameter set A is active CG 46CAGI p 23
97Parameter set B is active CG 47CAGI p 24
98Parameter set C is active CG 48CAGI p 25
99Parameter set D is active CG 49CAGI p 26
110Annunciations lost (buffer overflow) C 196 135130
112Annunciations for LSA lost C 76 135131
140General internal failure of device CG CAGI p 47
141Failure of internal 24 VDC power supplyCG 88 GI 135161
143Failure of internal 15 VDC power supplyCG 83 GI 135163
144Failure of internal 5 VDC power supply CG 89 GI 135164
145Failure of internal 0 VDC power supply CG 84 GI 135165
151Failure in I/O module 1 CG 91 GI 135166
152Failure in I/O module 2 CG 92 GI 135167
154Failure in the RKA module CG 90CAGI p 36
160Common alarm CG CAGI p 46
161Measured value supervision of currents CG CAGI p 32
163Failure: Current symmetry supervision CG 86 135183
301Fault in the power system CG 2 135231
302Fault event with consecutive number C 135232
391>Warning stage from Buchholz protectionCG 22 GI 150 41
392>Trip stage from Buchholz protection CG 21 GI 150 42
393>Tank supervision from Buchholz protec.CG 23 GI 150 43
501General fault detection of device C 142 BT150151
502General drop-off of device C 240 150152
511General trip of device C 230 BT150161
561Circuit breaker manually closed (pulse)CG 45 GI 150211
721Operat. meas. current L1 side 1 [%] is M 134145
¥©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©©©¦©©¦©©¦©©¦©©©¦©©©¾