$SSHQGL[87
9
&*&
1127 IN CT STP2 Prim. rated current of starpoint CT winding 2
min. 1 A
max. 100000 ©©©©
1128 CT2 EAR-PT Earth point formation of starpoint CT wind. 2
TOWARDS TRANSF. [ ] Towards transformer
TOWARDS EARTH [ ] Towards earth
1141 VECTOR GR3 Vector group numeral of winding 3
min. 0
max. 11 ©©©©
1142 UN WIND 3 Rated voltage of winding 3 of the transformer
min. 0.4 kV
max. 800.0 ©©©©
1143 PN WIND 3 Rated apparent power of winding 3
min. 0.2 MVA
max. 5000.0 ©©©©
1144 IN CT WIN3 Primary rated current of CT winding 3
min. 1 A
max. 100000 ©©©©
1145 CT3 STARPT Starpoint formation of CT winding 3
TOWARDS TRANSF. [ ] Towards transformer
TWDS.LINE/BUSBAR [ ] Towards line/busbar
1146 Io HANDLE Processing of zero sequence current of wind. 3
Io-ELIMINATION [ ] Io-elimination
Io-CORRECTION [ ] Io-correction
WITHOUT [ ] Without
1147 IN CT STP3 Prim. rated current of starpoint CT winding 3
min. 1 A
max. 100000 ©©©©
1148 CT3 EAR-PT Earth point formation of starpoint CT wind. 3
TOWARDS TRANSF. [ ] Towards transformer
TOWARDS EARTH [ ] Towards earth
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1200 GENERATOR OR MOTOR DATA
1202 UN GEN/MOT Rated voltage of the generator or motor
min. 0.4 kV
max. 800.0 ©©©©
1203 PN GEN/MOT Rated apparent power of generator/motor
min. 0.2 MVA
max. 5000.0 ©©©©
1206 CT STARPT Indication of polarity of the CT currents
SAME SIDE [ ] Same side
OPPOSITE SIDES [ ] Opposite sides
1207 IN CT 1 Primary rated current of CT side 1
min. 1 A
max. 100000 ©©©©