7411 T-PRE Pre-trigger time for fault recording
min. 0.05 s
max. 0.50 ©©©©
7412 T-POST Post-fault time for fault recording
min. 0.05 s
max. 0.50 ©©©©
7431 T-BINARY IN Storage time by initiation via binary input
min. 0.10 s
max. 5.00/Ñ ©©©©
7432 T-KEYBOARD Storage time by initiation via keyboard
min. 0.10 s
max. 5.00 ©©©©
7490 SYS LENGTH Length of fault record (former LSA)
660 VALUES FIX [ ] 660 values fix
<=3000 VAL. VAR [ ] <=3000 val. var
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
7800 SCOPE OF FUNCTIONS
7801 PROT. OBJ. Selection of the protected object
2WIND-TRANSF. [ ] 2winding-transformer
3WIND-TRANSF. [ ] 3winding-transformer
GENERATOR/MOTOR [ ] Generator/motor
2ENDS-BRANCH PT. [ ] 2ends-branch point
3ENDS-BRANCH PT. [ ] 3ends-branch point
1PHASE-TRANSF. [ ] 1phase-transformer
7806 STARPOINT A Selection of star point transformer A
NO ASSIGNMENT [ ] No assignment
SIDE 1 [ ] Side 1
SIDE 2 [ ] Side 2
SIDE3/V.OBJ []Side 3 / virt. obj.
7807 STARPOINT B Selection of star point transformer B
NO ASSIGNMENT [ ] No assignment
SIDE 1 [ ] Side 1
SIDE 2 [ ] Side 2
SIDE3/V.OBJ []Side 3 / virt. obj.
7816 DIFF PROT. Differential protection
EXIST [ ] Existent
NON-EXIST [ ] Non-existent
7819 REF PROT. Restricted earth fault protection
NON-EXIST [ ] Non-existent
WINDING 1 [ ] Winding 1
WINDING 2 [ ] Winding 2
WINDING 3 [ ] Winding 3
VIRTUAL OBJECT [ ] Virtual object
7821 BACK-UP O/C Back-up overcurrent protection
NON-EXIST [ ] Non-existent
REFERENCE SIDE1[]Reference side 1
REFERENCE SIDE2[]Reference side 2
REFERENCE SIDE3[]Reference side 3
VIRTUAL OBJECT [ ] Virtual object