Cycle and reaction times
5.6 Sample calculations
CPU 31xC and CPU 31x, Technical Data
5-24 Manual, 01/2006 Edition, A5E00105475-06
User Program
According to the instruction list, the user program runtime is 10.0 ms.
Calculating the cycle time
The cycle time for the example results from the following times:
User program execution time:
approx. 10 ms x CPU-specific factor 1.10 = approx. 11 ms
Process image transfer time
Process image of inputs: 100 μs + 16 bytes x 37 μs = approx. 0.7 ms
Process image of outputs: 100 μs + 6 bytes x 37 μs = approx. 0.3 ms
Operating system runtime at scan cycle checkpoint:
Approx. 0.5 ms
The sum of the listed times is equivalent to the cycle time:
Cycle time = 11.0 ms + 0.7 ms + 0.3 ms + 0.5 ms = 12.5 ms.
Calculation of the actual cycle time
Under consideration of communication load:
12.5 ms x 100 / (100-40) = 20.8 ms.
Thus, under consideration of time-sharing factors, the actual cycle time is 21 ms.
Calculation of the longest response time
Longest response time = 21 ms x 2 = 42 ms.
I/O delay
The maximum delay of the input digital module SM 321; DI 32 x 24 VDC is 4.8 ms per
channel.
The output delay of the digital output module SM 322; DO 16 x 24 VDC/0.5 A can be
neglected.
The analog input module SM 331; AI 8 x 12 bit was configured for an interference
suppression at 50 Hz. The result is a conversion time of 22 ms per channel. With the
eight active channels, the result is a cycle time of 176 ms for the analog input module.
The analog output module SM 332; AO 4 x 12-bit was programmed for the measuring
range of 0 ...10 Hz. This gives a conversion time of 0.8 ms per channel. Since 4
channels are active, the result is a cycle time of 3.2 ms. A settling time of 0.1 ms for a
resistive load must be added to this value. The result is a response time of 3.3 ms for
an analog output.
Neither PROFIBUS DP, nor PROFINET IO are being used, so you do not have to make
allowances for any DP cycle times on PROFIBUS DP or for PROFINET IO update times.

Table of Contents

Other manuals for Siemens CPU 313C-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C-2 DP and is the answer not in the manual?

Siemens CPU 313C-2 DP Specifications

General IconGeneral
BrandSiemens
ModelCPU 313C-2 DP
CategoryProcessor
LanguageEnglish

Related product manuals