Technical data of CPU 31xC
6.2 CPU 312C
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
6-5
Technical data
Number of function modules and communication
processors you can operate
FM
Max. 8
CP (PtP)
Max. 8
CP (LAN)
Max. 4
Time-of-day
Real-time clock Yes (SW clock)
Buffered
No
Accuracy
Deviation per day < 10 s
Behavior of the realtime clock after POWER
OFF
The clock keeps running, continuing at the time-
of-day it had when power was switched off.
Operating hours counter 1
Number
0
Value range
2
31
hours
(if SFC 101 is used)
Granularity
1 hour
Retentive
Yes; must be manually restarted after every
restart
Clock synchronization Yes
In the PLC
Master
On MPI
Master/slave
S7 signaling functions
Number of stations that can be logged on for
signaling functions
Max. 6
(depends on the number of connections
configured for PG / OP and S7 basic
communication)
Process diagnostics messages Yes
Simultaneously enabled interrupt S blocks
Max. 20
Testing and commissioning functions
Status/control variables Yes
Variables
Inputs, outputs, memory bits, DBs, timers,
counters
Number of variables
Of those as status variable
Of those as control variable
Max. 30
Max. 30
Max. 14
Forcing Yes
Variables
Inputs, outputs
Number of variables
Max. 10
Block status Yes
Single step Yes
Breakpoints 2
Diagnostic buffer Yes
Number of entries (not configurable)
Max. 100

Table of Contents

Other manuals for Siemens CPU 313C-2 DP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C-2 DP and is the answer not in the manual?

Siemens CPU 313C-2 DP Specifications

General IconGeneral
BrandSiemens
ModelCPU 313C-2 DP
CategoryProcessor
LanguageEnglish

Related product manuals