Technical data of CPU 31xC
6.4 CPU 313C-2 PtP and CPU 313C-2 DP
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
6-19
Technical data
CPU 313C-2 PtP CPU 313C-2 DP
DP slave
Number of connections 8
Services
PG/OP communication
Yes
Routing
Yes (only if interface is active)
Global data communication
No
S7 basic communication
No
S7 communication
No
Direct data exchange
Yes
Transmission rates
Up to 12 Mbaud
Automatic baud rate search
Yes (only if interface is passive)
Intermediate memory
244 bytes I / 244 bytes O
Address areas
Max. 32, with Max. 32 bytes each
DPV1
No
GSD file The latest GSD file is available at:
http://www.automation.siemens.com/
csi/gsd
Point-to-point connection
Transmission rates
38.4 Kbaud half duplex
19.2 Kbaud full duplex
Cable length
Max. 1200 m
User program can control the interface
Yes
The interface can trigger a break or an
interrupt in the user program
Yes (message with break ID)
Protocol driver
3964(R); ASCII
Programming CPU 313C-2 PtP CPU 313C-2 DP
Programming language LAD/FBD/STL
Instruction set see the Instruction List
Nesting levels 8
System functions (SFC) see the Instruction List
System function blocks (SFB) see the Instruction List
User program protection Yes
Integrated I/O CPU 313C-2 PtP CPU 313C-2 DP
Default addresses of the integrated
Digital inputs
Digital outputs
124.0 to 125.7
124.0 to 125.7
Integrated functions
Counters 3 channels (see the
Technological Functions
manual)
Frequency counter 3 channels up to Max. 30 kHz (see the
Technological Functions
manual)
Pulse outputs 3 channels pulse-width modulation up to Max. 2,5 kHz (see
Technological
Functions
manual)
Controlled positioning No

Table of Contents

Other manuals for Siemens CPU 314C-2 DP