Technical data of CPU 31x
7.8 CPU 319-3 PN/DP
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
7-43
Technical data
Analog channels
Inputs
4096
Outputs
4096
Inputs, central
256
Outputs, central
256
Removal
Racks, Max. 4
Modules per rack, Max. 8
Number of DP masters
Integrated
2
Via CP
4
Operable function modules and communication
processors
FM
8
CP (PtP)
8
CP (LAN)
10
Time
Clock
Hardware clock
Yes
Buffered
Yes
Buffered period
Typically 6 weeks (at an ambient temperature of
104 °F)
Behavior of the clock on expiration of the
buffered period
The clock keeps running, continuing at the time-
of-day it had when power was switched off.
Behavior of the realtime clock after POWER
ON
The clock continues running after POWER OFF.
Accuracy
Deviation per day: < 10 s
Operating hours counter
Number
4
Number
0 to 3
Value range
0 to 2
31
hours
(using the SFC 101)
Granularity
1 hour
Retentive
Yes; must be manually restarted after every
restart
Time synchronization
supported
Yes
In the AS
Master/slave
On MPI
Master/slave
on Ethernet via NTP
Yes (as client)
S7 message functions
Number of stations that can be logged on for
signaling functions
32
(depends on the number of connections
configured for PG / OP and S7 basic
communication)

Table of Contents

Other manuals for Siemens CPU 314C-2 PtP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 314C-2 PtP and is the answer not in the manual?

Siemens CPU 314C-2 PtP Specifications

General IconGeneral
BrandSiemens
ModelCPU 314C-2 PtP
CategoryProcessor
LanguageEnglish

Related product manuals