Mounting
Mount the transducer so that it is above the maximum material level by at least the
blanking value. Refer to the associated controller manual.
On liquid applications, mount the transducer face parallel to the liquid surface. On
solids applications, use a Siemens Milltronics Easy Aimer to help aim the
transducer.
Do not overtighten. Most applications require only hand tightening of the mounting
hardware. Connect a safety chain from the transducer to a structural member to
secure installation. Consider using the optional temperature sensor when a flanged
transducer is used, when a fast temperature response is required, or in high
temperature vessels.
Mounting – Solids Applications
WARNING: Special handling precautions must be taken to protect the
face of the transducer from any damage.
Note: For pressure tight applications, install transducers hand tight plus ½ turn to 1½ turns.
PTFE tape or other appropriate sealant may be used to aid in sealing the threads for use in
pressure applications.
WARNING: Improper installation may result in loss of process pressure.
Easy Aimer (typical model)
transducer
safety chain