10
Building Technologies
Fire Safety
A6V10207176_h_en_--
2016-05-23
Technical data
Mains voltage AC 115/230 V +10/-15 %
Power supply 150 W
Operating voltage DC 21…28.4 V
Operating current Max. 5 A
Battery capacity 2x 12 V, 26 Ah
Battery monitoring Yes
Network monitoring Yes
Connectable detector series Cerberus PRO FD720 (C-NET)
Number of lines
– Loops (with loop extension) or
– Stubs
4 (8)
8 (16)
Number of addresses Max. 504
Integrated inputs/outputs
– Relay output
– RT alarm
– RT fault
– Monitored outputs
– Alarm
– Fault
– Horn
– Freely programmable inputs/outputs
1
1
1
1
2
12
Operating unit Integrated
Slots for RS232, RS485 serial ports 2
Slots for network modules 2
Slots for loop extension 2
Mounting spaces for cable kit (communication) 2
Sounder module Max. 2
Ethernet port RJ45 1
Operating temperature -8…+42 °C
Storage temperature -20…+60 °C
Air humidity (no condensation permitted) ≤95 % rel.
Dimensions (W x H x D)
– Without cover cap
– With cover cap
430 x 796 x 160 mm
430 x 796 x 183 mm
Color
– Housing
– Cover cap
~RAL 7035, light gray
~RAL 000 50 00
Protection category (IEC 60529) IP30
Approvals
– VdS
– LPCB
– FM
– DNV GL (Marine)
G209077
126bn/07
3051081
See document A6V10339425