FDF221-9, FDF241-9 Flame detector (en)
FDL241-9 Linear smoke detector (en)
FDF221-9, FDF241-9 Detector de llamas
por infrarrojo (es)
FDL241-9 Detector lineal de humo (es)
FDF221-9, FDF241-9 Flammenmelder (de)
FDL241-9 Linearer Rauchmelder (de)
FDF221-9, FDF241-9 Rivelatore di
fiamma (it)
FDL241-9 Rivelatore lineare di fumo (it)
FDF221-9, FDF241-9 Détecteur de flammes
à infrarouge (fr)
FDL241-9 Détecteur linéaire de fumée (fr)
Commissioning en
Inbetriebnahme de
Mise en service fr
Puesta en servicio es
Messa in servizio it
LI N E
+
+
Fig. 1
en
Commissioning
FDF221-9, FDF241-9 Flame detector
FDL241-9 Linear smoke detector
General Information
The flame detector and the linear smoke detector are
delivered ex works in FDnet mode.
For individual collective control panels an automatic
switchover from FDnet mode to collective mode is not
possible. Therefore, detectors must be switched to
collective mode by means of a DC source. Switchover
from collective to FDnet mode is always performed
automatically.
Switching over to collective mode
Prerequisite
To switch over, use an original base that is not connected
to the detector line.
- Base FDFB291 for FDF
- Base FDLB291 for FDL
Procedure
Electric voltage!
Take into account the positive and negative poles!
Detector may be damaged.
1. Connect the corresponding base to a 12-28 VDC
source (e.g. battery) according to the connection
diagram (see Fig. 1).
2. Place the detector in the base during approx. 15
seconds.
The detector is switched over to collective mode and can
now be installed on the collective line.

Other manuals for Siemens FDF241-9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDF241-9 and is the answer not in the manual?

Siemens FDF241-9 Specifications

General IconGeneral
CategorySecurity Sensors
TypeFlame Detector
Power Supply24 V DC
Field of View90°
Degree of protectionIP66
Protection RatingIP66
Detection MethodIR
Humidity Range95% RH, non-condensing
CommunicationRelay output
CertificationsEN 54-10
Detection RangeUp to 25 m