EasyManua.ls Logo

Siemens Flowrite 599 SKD62U - Advanced Operation and Wiring; DIP Switch Functions; Valve Operation Modes

Siemens Flowrite 599 SKD62U
11 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SKD6xU Electronic Valve Actuators 24 Vac Proportional Control Technical Instructions
Document Number 155-180P25
February 28, 2018
Siemens Industry, Inc. Page 7
Start-up, Continued
1 2
Figure 11. SKD Electronic Features.
DIP Switches
(Left to right)
1
Selection of
Control Signal
2
Selection of
Flow Characteristic
ON 4 to 20 mA Modified*
OFF
Factory Setting
0 to 10 Vdc Default
*Changing the default setting will modify an equal percentage valve to a linear flow
characteristic. When set to default, the flow characteristic is determined by the valve body.
Normally Closed Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve opens.
Inward (1 to 0): Valve closes.
Normally Open Valve
Actuator pressure cylinder moves:
Outward (0 to 1): Valve closes.
Inward (1 to 0): Valve opens.
Three-Way Valve
Actuator pressure cylinder moves
Outward (0 to 1): Valve opens between port NC and C.
Inward (1 to 0): Valve opens between ports NO and C.
The measuring voltage at terminal U provides valve stem position feedback to an
indicating instrument or building automation system.