21/25 
Building Technologies Division    CC1N7451en 
  20.11.2017 
Connection examples and program sequence 
Doubling the safety time with direct 
spark flame burners 
16
Z
N
17
18
BV1
19
BV2
7451a10/1295
 
Only with burner controls of the 01 
series. 
 
This circuit change (linking terminals 
17 and 18) reduces the preignition 
time by 50 %. 
 
 
Extension of the safety time is only permitted if in compliance with the 
relevant national standards. 
 
Burner without air damper 
11
10
86
7451a11/0396
M
N
 
If the case of burners with no air 
damper (or with an air damper not 
controlled and monitored by the 
burner control), terminals 8 and 6 
must be linked, as otherwise the 
burner control will not be able to start 
the burner. 
 
Reversed polarity protection with 
AGM30 
GM30
 1    23
Black
Brown
If the mains cables (L-N) are 
switched, the AGM30 simulates a 
flame signal (extraneous light). The 
burner initiates lockout. 
 
2-stage direct spark flame burner
 
 
16
Z
N
17
18
BV1
BV2
SA
LR
19
9
20
11
10
8
LK
11
7
1
6
5
2
10
8
9
4
3
N
12
13
IV
I
M
II
III
7451a03/0396
L...
LR
SA
BV1/BV2
 
Load control by a 2-position controller. The air damper is 
closed during burner off periods. 
 
min.
0...
100%
R
M1
M2
Z
BV1
LR
BV2
FS
A
B
C
D
7451a06/0600
T
P
M
R
M
LK
~
t7 t1
t6
t3
TSA
t4
t5
t11
t12
t13
Control of actuator «SA» according to the single-wire 
principle (actuator «SA»: E.g. SQN3... according to Data 
Sheet N7808). For other connections, refer to 
«Connection diagrams».