Function (cont´d)
When the switch-on command is given, the auxiliary fan starts to run. When the air
pressure switch closes its contact, the heating coil of the bimetal sequencing device is
energized and the bimetal pushes contact set «c, d, e» towards «f» (thereby opening «f
- g»). On completion of the prepurge time, «e - f» is closed so that both fuel valve
«BV1» and the ignition transformer receive voltage: The safety time starts. On flame
establishment, the flame relay latches mechanically «e - f», pushes «c» back at the
same time and opens «fr». The ignition transformer is thus switched off and the heating
coil deenergized, so that «d» can revert to its starting position. When tilting back, «g - f»
closes so that the main valve «BV2» receives voltage.
If no flame signal is generated, the flame relay does not open «c - d», so that the
bimetal will continue to be heated. The bimetal thus continues to bend until – tilting – it
actuates contact «tz2»: Lockout
In the event of an erroneous premature flame signal, the flame relay – by means of its
latch – prevents «e - f» from making, which means no release of fuel. «TZ», however,
still receives power so that the bimetal continues to bend until, eventually; lockout is
initiated by «tz2».
EK
1
2
10
8
7
11 9 6 4 5 12
7418i01/0304
SB
W
R
L
N
AL
M
1)
Z
LP
BV1
ION
L1
X
Y
Z
tz2
a
b
fr
TZ
c
d
e
tz1
f
g
FR
LGA52... / 63...
BV2
Si
H
AL Fault status signal H Main switch
BV... Fuel valve M Auxiliary fan
EK Lockout reset button R Thermostat or pressurestat
ION Ionization probe SB Safety limit thermostat
FR Flame relay Si External primary fuse
L1 Built-in lockout warning lamp TZ Electro-thermal timer
LP Air pressure switch (bimetal system) with contacts «tz»
W Limit thermostat
/ pressure switch
1) Not monitored to EN 298
Z Ignition transformer
Internal diagram
LGA52... / LGA63...
Legend