6.2 OSDP Reader wiring
Reader connection via OSDP with or without encryption. The readers should be
connected to the appropriate terminal blocks (A, B, -, +) of the READER port
Mapping from MFI board to the Reader ports.
Up to 8 OSDP readers can be daisy chained (from one reader to another) on the
same connection.
Labels on
MFI board
A
B
-
+
Labels on the
Reader ports
(HID,
Vanderbilt
Readers)
GPIO 1
A
GPIO 2
B
GND
-
+VDC
+
6.3 Wiring of monitored input
1. Connect the shielding to the housing earth.
2. Insulate the shielding at the input (e.g. door contact), do not connect it.
3. DC: door contact
4. R: terminating resistors each 22 kOhm
6.4 LEDs
LED function
Name on the board
Color of LED
RLY 1
Status LEDs
Indicates
activated/deactivated
H715
White
RLY 2
H716
White
RLY 3
H717
White
RLY 4
H718
White
AUX OUT 1
H719
White
AUX OUT 2
H720
White
AUX OUT 3
H721
White
AUX OUT 4
H722
White
INPUT status LEDs
H700 to H707
Red (During tamper)
Green (Normal)
Orange (Alarm)