Basic steps for calculating the SCCR of a control panel
4.1 SB4.2 Determining the short-circuit current ratings (SCCR) of individual power circuit components
Short-circuit current rating (SCCR) of industrial control panels
Reference Manual, 06/2013, A5E31896849002A/RS-AA/001
17
Example
The following example shows a circuit breaker according to UL489 in a feeder circuit and a
tested combination according to UL508 Type F. The circuit breaker has been tested and
approved for 100 kA and the self protected combination motor controller per UL 508 Type E
has also been tested and approved for 65 kA.
The combination shown below complies with 65 kA according to the UL rules.
Figure 4-8 Example combination