12
Factory Assembled Panelboards
Selection and Application - Type P1
SELECTION
Breaker
Type
Amp
Rating
Available
Trip Values
100
BL 10 BL 30, 40, 50, 60, 70, 80, 90, 100
BLH 22 LH 30, 40, 50, 60, 70, 80, 90, 100
HBL 65 HL 30, 40, 50, 60, 70, 80, 90, 100
ED2 10 E2 30, 40, 50, 60, 70, 80, 90, 100
65 14 BD 30, 40, 50, 60, 70,
BQD6 10
125
ED4 65 18 E4 30, 40, 50, 60, 70, 80, 90, 100, 110, 125
ED6 65 25 18 E6 30, 40, 50, 60, 70, 80, 90, 100, 110, 125
HED4 100 42 H4 30, 40, 50, 60, 70, 80, 90, 100, 110, 125
250
FXD6 65 35 18 FX 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
FD6 65 35 18 F6 250
HFD6 100 65 25 HF 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250
400
JXD6 65 35 25 JX 200, 225, 250, 300, 350, 400
JD6 65 35 25 J6 200, 225, 250, 300,
350, 400
HJD6 100 65 35 HJ 200, 225, 250, 300, 350, 400
HHJD6 200 100 50 HH 200, 225, 250, 300, 350, 400
225
QJ2 10 QJ 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJH2 22 QH 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
QJ2-H 42 Q2 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
FD6 65 35 18 F6 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
FXD6 65 35 FX 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
HFD6 100 65 HF 70, 80, 90, 100, 110, 125, 150, 175, 200, 225
Max. Interrupting
Rating (kA)
Catalog
No.
480Y/277V
240V
600Y/347V
18
25
60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225,
Main Breaker Selection
No. of
Poles
Amp
Rating
240V Max
Breaker
Frame
   
BL
  
   
BLH
   
   
HBL
   
BLF
  
   
BLHF
   
   
#(-    
BLE
  
   
#2%     
Branch Breaker Selection
480Y/277V/600Y/347V
Max. Interrupting Rating (kA)
10
22

10
22
10
'PSEFUBJMFEDJSDVJUCSFBLFSJOGPSNBUJPOQMFBTFDPOTVMU4FDUJPO
'PSi4FSJFT3BUJOHwUFTUFEDPNCJOBUJPOTQMFBTFDPOTVMUUIF4JFNFOT4FSJFT3BUFE$PNCJOBUJPO(VJEF@@"*4@