Siemens Master room unit QAX850 CE1N2722en
Building Technologies 28.08.2007
Electromagnetic compatibility
Immunity domestic section, light industry
Emissions domestic section, light industry
EN 61 000-6-1
EN 61 000-6-3
-conformity
EMC directive
Low-voltage directive
89/336/EEC
73/23/EEC
N474
conformity to
Australian EMC framework
Radio interference emission Standard
Radio Communication Act 1992
AS/NZS 4251.1
Measuring range 0…49 °C
Room temperature
measurement
Setpoint range 5…35 °C
Accuracy at 20 °C max. ±0.5 K
Temperature calibration range max. ±3.0 K in increments of 0.5 K
Room temperature display resolution 0.5 K
Weight
Excluding packaging approx. 0.1 kg
Notes
The products may only be used in building services plant and applications as
described above.
When using the products, all requirements specified under ”Technical data” must be
observed.
Local regulations for electrical installations must be complied with.
Connection diagram
N1
A1
HB+
HB-
HB+
HB-
2723A01
A1 QAX850 master room unit
N2 RRV… controller
Product liability