EMC and Environmental Type Tests 43
Test Description Test Levels Severity Levels
IEC 60068-2-14 Change of Temperature Test Nb 5 Cycles, -40 to 85°
C (40 to 185° F)
IEC 60068-2-30 Humidity (Damp
Heat, Cyclic)
Test Db 93% upper temperature,
97% lower temperature
55 °C (131 °F), 6 Cycles
IEC 60068-2-78 Humidity (Damp
Heat, Steady State)
Test Cab 10 days @ 55 °C (131 °F)
and 93% Relative Humidity
IEC 60255-21-1 Vibration Level 2 (2 g @ 10 to 150 Hz) Class 2
Shock Level 2 (30 g @ 11 mS) Class 2IEC 60255-21-2
Bump Level 1 (10 g @ 16 mS) Class 1
IEC 60255-21-3 Seismic Method A, Class 2 Class 2
IEC 60529 Ingress Protection IP4x
IEC 60068-2-31 Free Fall Test Ec 25 cm