3.6 Manual operation
The RVL471 can be switched to manual operation. In this case, the control will be
switched off. In manual operation, the various actuating devices behave as follows:
Heating circuit mixing valve: This mixing valve is not under voltage, but can be manu-
ally driven to any position by pressing the manual buttons
( = closing,
= opening). The heating circuit pump / circulating pump is continuously running.
Boiler: The 2 burner stages are continuously on. The manual button
can be used to
switch the second stage on and off. Pump M1 is continuously running
D.h.w. charging pump: The charging pump is continuously running
D.h.w. changeover valve: The diverting valve is always in the Heating circuit position
D.h.w. slipper / seat valve: This valve is driven to the fully closed position, in which
case the closing time is five times the set running time. Then, it is deactivated
Circulating pump M4: Continuously running
Electric immersion heater K6: Continuously released
Multifunctional relay: Continuously energized
Manual operation also negates any overriding of the controller's operating mode
(bridging of H1M).
3.7 Plant type and operating mode
Depending on the selected type of plant, the following operating modes are available:
Plant type
10 YES YES YES YES NO YES
11, 12, 14, 15 YES YES YES YES YES YES
20 YES YES YES YES NO YES
21, 22, 23, 25 YES YES YES YES YES YES
30 YES YES YES YES NO YES
31, 32, 33, 34, 35 YES YES YES YES YES YES
40 YES NO NO NO NO YES
41, 42, 45 YES NO NO NO YES YES
50 YES NO NO *) NO YES
51, 52, 54, 55 YES NO NO *) YES YES
60 YES NO NO NO NO YES
61, 62, 65 YES NO NO NO YES YES
*)
Depending on the boiler's operating mode:
Boiler with automatic shutdown: NO
Boiler with manual shutdown: YES