PROFINET IO
6.3 Metering values, addressing und data traffic
3WA Air Circuit Breaker Communication
56 System Manual, 11/2021, 92310000004-02
Control bytes
The control bytes for controlling the circuit breaker are always two bytes long. With these
control bytes, you can:
• Open/close the circuit breaker
• Acknowledge tripping events
Setting the outputs is edge-triggered. It suffices to set the corresponding bits for 0.5 s. After
this, these control bits must be reset to avoid subsequently triggering any undesired actions.
The table below contains a description of the control bytes:
Commands to close/open the circuit breaker
Circuit breaker open (opening of main contacts)
Circuit breaker closed (closing of main contacts)
Acknowledge and reset currently active trip indication
Reset all minimum/maximum value logs (except temperature)
Reset minimum/maximum logs for temperatures