EasyManua.ls Logo

Siemens SENTRON 3WL - Page 30

Siemens SENTRON 3WL
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
30
Siemens · 2009
Size I to III
Type
3WL1
Auxiliary releases
Shunt release (ST)
(F1, F2)
For continuous command
(100 % ON period), locks
out on momentary-con-
tact commands
- Response value pickup
> 0.7 × U
s
(circuit breaker is tripped)
- Operating range
0.85 ... 1.1 × U
s
- Extended operating range
for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
0.7 ... 1.26 × U
s
- Rated control supply voltage U
s
AC 50/60 Hz
DC
V
V
110; 230
24; 30; 48; 60; 110; 220
- Power consumption AC/DC VA/W
15/15
- Minimum command duration at U
s
ms 60
- opening time of circuit breaker at
U
s
= 100 %
AC/DC ms
80
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational
class)/ miniature circuit breaker with C characteristic
1 A TDz (slow)/1 A
5 % ON period - Response value Pickup
> 0.7 × U
s
(circuit breaker is tripped)
- Operating range
0.85 ... 1.1 × U
s
- Extended operating range
for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
0.7 ... 1.26 × U
s
- Rated control supply voltage U
s
AC 50/60 Hz
DC
V
V
110 ... 127; 208 ... 240
24; 48; 110 ... 125; 220 ... 250
- Power consumption AC/DC VA/W
15/15
- Minimum command duration at U
s
ms 25
- Opening time of circuit breaker at
U
s
= 100 %
AC/DC ms
50
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational
class)/miniature circuit breaker with C characteristic
1 A TDz (slow)/1 A
With stored energy
feature consisting of
shunt release and capa-
citor storage device
- Rated control supply voltage U
s
AC 50/60 Hz
DC
V
V
110; 230
110; 220
- Operating range
0.85 ... 1.1 × U
s
- Power consumption AC/DC VA/W 1/1
- Storage time at U
s
/
recharging time at U
s
maximum 5 min/minimum 5 s
- Opening time of circuit breaker,
short-circuit protection
As with "for continuous
command"
Remote reset solenoid for mechanical tripped indicator (F7)
Remote reset solenoid for
mechanical tripped indica-
tor (F7)
- Operating range
0.85 ... 1.1 × U
s
- Extended operating range
for battery operation
At 24 V DC, 48 V DC
110 V DC
220 V DC
0.7 ... 1.26 × U
s
- Power consumption AC/DC VA/W 50/50
- Minimum command duration at U
s
for the remote
reset solenoid
ms 60
- Short-circuit protection
Smallest permissible DIAZED fuse (gL operational class)/
miniature circuit breaker with C characteristic
2 A TDz (slow)/1 A at 24 V DC
and 48 V DC,
1 A TDz (slow)/1 A at 110 V and
208 ... 250 V
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage U
i
V AC/DC 500
Rated operational voltage U
e
V AC/DC 500
Rated impulse withstand voltage U
imp
kV 4
Switching capacity Alternating current
50/60 Hz
- Rated operational voltage U
e
- Rated operational current
I
e
/AC-12
I
e
/AC-15
V
A
A
24 ... 230
10
4
380/400
10
3
500
10
2
Direct current - Rated operational voltage U
e
- Rated operational current
I
e
/DC-12
I
e
/DC-13
V
A
A
24
10
8
48
8
4
110
3.5
1.2
220
1
0.4
Short-circuit protection Largest permissible DIAZED fuse (gL operational class)
Largest permissible miniature circuit breaker with C characteristic
10 A TDz, 10 A Dz
10 A

Other manuals for Siemens SENTRON 3WL