Description
3.2 Measuring inputs
7KT multimeter
14 Manual, 08/2018, 2514284149-01
Device damage due to DC current
The device is not suitable for measuring DC current.
Only measure AC current with the device.
The devices are designed for a rated current of 1 A or 5 A for connecting standard current
transformers.
Ampacity of current measuring inputs
The current measuring inputs can be continuously loaded as follows:
● With 1.2 A at a rated current of 1 A
● With 6 A at a rated current of 5 A
Device damage due to DC current
The device is not suitable for measuring DC current.
Only measure AC current with the device.
The device is designed for:
● Direct measurement on the grid
● Nominal voltage 364 V/600 V