System Messages
C-16
TP 170A Equipment Manual
Release 12/99
RemedyEffect/CauseNumber
290005 This message is issued when message
number 290002 is triggered more than five
times.
In this case, no further individual messages
are generated.
Check the value range or type of the
variable.
290006 The threshold values configured for the tag
have been violated by values entered.
Observe the configured or current threshold
value of the tag.
290007 There is a difference between the source
and target structure of the recipe currently
being processed. The target structure
contains an additional data record tag which
is not available in the source structure.
The data record tag specified is assigned its
start value.
Insert the specified data record tag in the
source structure.
290008 There is a difference between the source
and target structure of the recipe currently
being processed. The source structure
contains an additional data record tag which
is not available in the target structure and
therefore cannot be assigned.
The value is rejected.
Remove the specified data record tag in the
specified recipe from the project.
290010 The storage location configured for the
recipe is not permitted.
Possible cause:
Impermissible characters, write protected,
data medium full or does not exist.
Check the path specification configured.
290011 The data record specified by the number
does not exist.
Check the source for the number (constant
or variable value).
290012 The recipe specified by the number does not
exist.
Check the source for the number (constant
or variable value).
290013 An attempt was made to save a data record
under a data record number which already
exists.
The process is not executed.
S Check the source for the number
(constant or variable value).
S Delete the data record beforehand.
S Change the function parameter
“Overwrite”.
290014 The file specified to be imported could not be
found.
S Check the file name.
S Ensure that the file is in the specified
directory.
290020 Acknowledgement that downloading of data
records from operating unit to PLC has
started.
–
290021 Acknowledgement that downloading of data
records from operating unit to PLC has been
completed without any errors.
–