EasyManuals Logo
Home>Siemens>Control Panel>SIMATIC HMI TP1900 Comfort

Siemens SIMATIC HMI TP1900 Comfort User Manual

Siemens SIMATIC HMI TP1900 Comfort
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #98 background imageLoading...
Page #98 background image
Commissioning the device
4.3 Parameter assignment for Comfort Panel
Comfort Panels
98 Operating Instructions, 07/2017, A5E36770603-AB
4. "Digital signatures" group:
To select the check of the signature during transfer of an HMI device image, select the
"Validate Signatures" check box. This function is available in connection with an HMI
device image that is compatible with WinCC (TIA Portal) V14 or higher. Image signatures
are checked starting with V14. If you transfer an image that is compatible with a version
before V14, an error message is displayed.
To transfer an unsigned image that is compatible with a version before V14, clear the
"Validate Signatures" check box.
5. Select the required data channel in the "Transfer channel" group.
PN/IE
The transfer takes place over PROFINET or Industrial Ethernet. An HMI device can
communicate as follows:
With a PLC directly via routing
Over a switch or over a router in the local network
MPI
PROFIBUS
USB device (with Comfort V1/V1.1 devices)
Ethernet
6. To call up the addressing of the HMI device, press "Properties".
The necessary inputs can be found in the following sections, depending on the data
channel:
PN/IE: see section "Entering the IP address and name server (Page 121)".
MPI or PROFIBUS: see section "Changing MPI/PROFIBUS DP settings (Page 124)".
7. Confirm your entries with "OK".
The dialog closes.
The data channel for transfer is configured.
See also
Load project from external storage medium (Page 142)

Table of Contents

Other manuals for Siemens SIMATIC HMI TP1900 Comfort

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI TP1900 Comfort and is the answer not in the manual?

Siemens SIMATIC HMI TP1900 Comfort Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC HMI TP1900 Comfort
CategoryControl Panel
LanguageEnglish

Related product manuals