6 Technical specifications
Input
Only for connecting to alternating voltage systems!
Power consumption of the measuring circuit
0.3 VA with IAN = 2.5 mA
0.4 VA with I
AN = 5 mA
0.6 VA with I
AN = 10 mA
Permissible modulation range
EN
EN
E
Input transducer
Alternating current
Standard rated currents IEN
Continuous overload capacity
for I
EN = 1 A; 1.2 A
for I
EN = 1.5 A
for I
EN = 2 A; 2.4 A
for I
EN = 2.5 A
for I
EN = 5 A; 6 A
for I
EN = 7.5 A
EN
2 A
3 A
4 A
5 A
10 A
12 A
Surge overload capacity
for I
EN = 1 A; 1.2 A; 1.5 A;
for I
EN = 2 A; 2.4 A; 2.5 A
for IEN = 5 A; 6 A; 7.5 A; 10 A
50 A for 1 s
100 A for 1s
Input transducer
EN
in the range from 40 to 500 V
Continuous overload capacity
EN
(5 surges 1s, in intervals of 5s)
Output
Output signal bipolar, short-circuit proof and resistant to no-load operation, optionally load-independent
direct current or load-independent direct voltage
AN
2.5 mA; 5 mA; 10 mA; 20 mA
Special rated current IAN
in the range from 1 to 20 mA
Permissible modulation range
AL
B
AN
Residual ripple ISS ≤ 0.5% SS of IAN
Setting time tgg
– Transducer alternating current
– Transducer alternating voltage
≤ 1 s