PLC alarms
11/2006 Overview of Alarms
2-813
© Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
400143 Delete DB 43 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400144 Delete DB 44 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400145 Delete DB 45 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400146 Delete DB 46 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400147 Delete DB 47 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400148 Delete DB 48 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal
400149 Delete DB 49 in the PLC and restart
Definitions: The DB created by the basic program and the existing DB differ in size.
Reaction: Alarm display.
Remedy: Displayed DB must be deleted via STEP7. Possibly max. program size of the user program exceeded.
Program
Continuation:
Internal

Other manuals for Siemens Simodrive 611

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Simodrive 611 and is the answer not in the manual?

Siemens Simodrive 611 Specifications

General IconGeneral
BrandSiemens
ModelSimodrive 611
CategoryMedia Converter
LanguageEnglish

Related product manuals