IFP-1000 Basic Operating Instructions
These instructions must be framed and displayed next to the IFP-1000 panel in accordance with NFPA 72
fire code for Local Protected Fire Alarm Systems.
Operation Keystrokes
Silence alarms and
troubles
Press then rotate the key or enter a code
Reset alarms
Press then rotate the key or enter a code.
Conduct a fire drill
1. Rotate the key or enter a code then press to access the menu.
2. Press .
3. Press to select Fire Drill.
4. Press any key to begin the drill. To end the drill, press any key.
To conduct a fire drill from a remote fire drill switch:
Activate the switch to begin the drill; de-activate the switch to end the drill.
View alarms and
troubles
When the system is in alarm or trouble, press to view location and type of alarm or trouble.
Check detector
sensitivity
1. Rotate the key or enter a code then press to access the menu.
2. Press
.
3. Press for Point Status.
4. From the list that displays, use the or to select the module you want, then press . Then
key in the point number you want to view and press .
5. The fourth line of the display shows the sensitivity status.
“NORMAL” means the detector is in compliance with NFPA 72.
“CAL MAINT” means the detector is in compliance with NFPA 72 but
maintenance should be performed soon.
“CAL TRBLE” means the detector is not in compliance with NFPA 72.
Set Time and Date
1. Rotate the key or enter a code then press to access the menu.
2. Press .
3. Make changes in the fields on the screen as necessary.
4. When the time and date are correct, press .
Enable / Disable point
1. Rotate the key or enter a code then press to access the menu.
2. Press for Point Functions.
3. Press for Disable / Enable point.
4. Press for Disable / Enable point.
5. From the list that displays, use the or to select the module you want, then press . Then
key in the point number you want to disable or enable and press
.
6. Press to toggle the point between NORMAL (enabled) and DISABLE.
View event history
Rotate the key or enter a code then press to access the menu, then press to select Event
History. Events will display in date order, with most recent events displaying first.
Form #: 151156 Rev. B, 12/05
SILENCE
RESET
ENTER
1
1
ENTER
2
2
ENTER
ENTER
ENTER
4
ENTER
ENTER
2
1
7
ENTER
ENTER
ENTER
3

Questions and Answers: