EasyManua.ls Logo

Sime Format.zip 25 BF - 4.4 ADJUSTMENT OF HEAT OUTPUT FOR C.H. MODE

Sime Format.zip 25 BF
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
85
value given in Table 4: to reduce the
pressure, turn the nut counterclockwi-
se; to increase the pressure, turn it
clockwise.
Operate the main switch a number of
times, keeping the hot water tap open
all the time, and check that the pressu-
re corresponds to the values given in
Table 4.
After having adjusted the maximum pres-
sure, calibrate the minimum pressure as
follows:
Disconnect the electric power to the
modulator.
With the D.H.W. potentiometer knob on
maximum, the D.H.W. cock open and the
burner ignited, turn the screw (2) keeping
locked the nut (3) to achieve the mini-
mum pressure value given in Table 4:
to reduce the pressure, turn the screw
counterclockwise; to increase the pressu-
re, turn it clockwise.
Operate the main switch a number of
times, keeping the D.H.W. tap open all the
time, and check that the pressure corre-
sponds to the values given in Table 4.
Restore electric power to the modulator.
Replace the plastic cap (1) in position.
4.3.2 Pressure adjustment
HONEYWELL VK 4105M (fig. 20/b)
To set the maximum pressure, proceed as
follows :
Connect the pressure column to the pres-
sure inlet downstream of the gas valve.
For the “BF” models connect the pressu-
re column as shown in fig. 20.
Remove the plastic cap on the modula-
tor (1).
Set the knob of the D.H.W. potentiome-
ter to the maximum value.
Ignite the boiler and open the D.H.W. cock.
Using a ø 9 spanner, turn the nut (3) to
achieve the maximum pressure value
given in
Table 4
: to reduce the pressure,
turn the nut counterclockwise; to increa-
se the pressure, turn it clockwise.
Operate the main switch a number of
times, keeping the D.H.W. cock open all the
time, and check that the pressure corre-
sponds to the values given in Table 4.
After adjusting maximum pressure, pro-
ceed to calibrate minimum pressure:
Disconnect the electric power supply
from the modulator.
With the hot water potentiometer
knob set to the maximum, the hot
water tap turned on and the burner lit,
hold nut (3) locked in place and simulta-
neously turn nut (2) using a fixed ø 7
wrench to identify the minimum pres-
sure value shown in Table 4: turn the
nut anti-clockwise to reduce pressure
or clockwise to increase it.
Turn the boiler on and off repeatedly
while keeping the hot water tap turned
on, checking that pressure corresponds
to the values shown in Table 4.
Connect up the power supply to the
modulator again.
Replace the plastic cap (1).
4.4 ADJUSTMENT OF HEAT
OUTPUT FOR C.H. MODE
To adjust boiler heat output for heating pur-
poses, i.e., modifying the setting made at
the factory which is approximately 16 kW
for “25” and 20 kW for “30”, use a screw-
driver to adjust the C.H. heat output trim-
mer (1 fig. 15).
To increase working pressure, turn the
trimmer clockwise; to reduce pressure,
turn the trimmer counterclockwise.
To facilitate the operations of adjusting
heat output, see the pressure/heat output
diagrams for natural gas (methane) and
butane or propane gas (figg. 21 - 21/a -
21/b).
Fig. 20/b
KEY
1 Plastic tap
2 Minimum pressure adjusting nut
3 Maximum pressure adjusting nut
11
10
9
8
7
6
5
4
3
2
1
8,1 (7.000) 11,6 (10.000) 17,4 (15.000) 23,2 (20.000)
POTENZA TERMICA kW (kcal/h)
PRESSIONE UGELLO mbar
29,0 (25.000)
25
30
12
13
25
20
15
10
8,1 (7.000) 11,6 (10.000) 17,4 (15.000) 23,2 (20.000)
POTENZA TERMICA kW (kcal/h)
PRESSIONE UGELLO mbar
30
5
29,0 (25.000)
25
30
Fig. 21/a
Fig. 21
Pressure/heat output diagram for natural gas (methane)
HEAT OUTPUT kW (kcal/h)
NOZZLE PRESSURE mbar
Pressure/heat output diagram for butane gas (G30)
NOZZLE PRESSURE mbar
HEAT OUTPUT kW (kcal/h)

Related product manuals