2100 System Overview
CHANNEL 1 = MONITOR POINTS l- 64 + CONTROL POINTS l- 48
CHANNEL 2 = MONITOR POINTS 65-128 + CONTROL POINTS 49- 96
CHANNEL 3 = MONITOR POINTS 129-192 + CONTROL POINTS 97-144
CHANNEL 4 = MONITOR POINTS 193-256 + CONTROL POINTS 145-192
CHANNEL 5 = MONITOR POINTS 257-320 + CONTROL POINTS 193-240
CHANNEL 6 = MONITOR
POINTS 321-384 + CONTROL POINTS 241-288
CHANNEL 7 = MONITOR POINTS 385-448 + CONTROL POINTS 289-336
CHANNEL 8 = MONITOR POINTS 449-512 + CONTROL POINTS 337-384
A 2106 system can have up to 8 channels using separate communication lines for each channel.
Each 2100 encoder has 4 monitor points and 3 control points.
Each 2100 transponder can have up to 40 monitor points and 36 control points for a total of 10
encoders within the same 6 unit cabinet.
Maximum of 16 encoders for a total of 64 monitor points and 48 control points per channel.
Maximum of 10 encoders in a 6 unit cabinet.
Maximum of 6 encoders in a 4 unit cabinet.
Maximum of 3 encoders in a 2 unit cabinet.
In converting the 2100 system to a 2120 configuration, the existing four to eight 2100 channels will be reduced
to one or two 2120 channels (depending on the system requirements).
l
This will necessitate communication line wiring and hardware changes.
5