2100 Multiplex
Jumper Placement
and Switch Settings
aSimplex
0 1~7S~W*XlhOR0WrdwC0., Gardner, Mass.01441-0001 U.S.A.
MUX1 -21-002
Ed587
firealarmresources.com

Other manuals for Simplex 2100

Question and Answer IconNeed help?

Do you have a question about the Simplex 2100 and is the answer not in the manual?

Summary

Jumper Placement Configuration

Transponder Jumper Placement

Determines jumper placement for transponders using specification sheets.

Transponder Monitor Point Operation

Explains NORMAL, LATCH, and KEY modes for monitor points using jumpers.

Transponder Control Point Status

Details setting control circuit status (NO/NC) via jumper wires on zone boards.

Transponder Monitor Point Status

Describes setting monitor point status (NO/NC) using jumper holes on encoder boards.

Encoder Board Address Settings

Explains how to set encoder addresses using binary code and jumpers.

Transponder Baud Rate

Details setting transponder baud rates via jumper placement on the motherboard.

Central Control Console Configuration

Central Control Console Channel & Annunciator Baud Rate

Covers setting baud rates for console communication channels and annunciators.

Central Consoles Printer & CRT Baud Rate

Explains jumper settings for console printer and CRT baud rates.

Switch Settings

General Switch Settings

Notes that only Printer and CRT switches may require verification or changes.

CRT Switch Settings

Details important CRT switches located on the Logic Printed Circuit Board.

Console Printer Settings

Okidata Printer Settings

Provides switch settings for the Okidata 110 printer used in the multiplex system.

Centronics 730-3 Printer Settings

Details switch settings for the Centronics 730-3 printer used in the multiplex system.

Overview

The Simplex 2100 Multiplex system is a sophisticated fire alarm and control system designed for comprehensive monitoring and management of various points within a facility. This manual provides detailed information on jumper placement and switch settings, crucial for both initial installation verification and subsequent modification of the system's operational parameters. The system utilizes transponders, central control consoles, and various peripheral devices like printers and CRTs to achieve its functionality.

Function Description

The Simplex 2100 Multiplex system serves as a centralized control and monitoring platform for fire alarm and other building management functions. It employs transponders to collect data from monitor points (e.g., smoke detectors, pull stations, security devices) and to activate control points (e.g., emergency generators, fire signals, HVAC systems). The central control console acts as the primary interface for system operators, displaying status information, logging events, and allowing for manual control actions. The system's multiplexing capability allows for efficient communication over a single channel, reducing wiring complexity.

Key Components and Their Functions:

  • Transponders: These are distributed units that interface directly with sensing devices (monitor points) and controlled devices (control points). Each transponder has a unique channel and transponder number, and can contain multiple encoders.
  • Encoders: Within each transponder, encoders are responsible for processing signals from groups of monitor and control points. Each encoder has a unique address.
  • Monitor Points: These are input points connected to sensors that detect various conditions (e.g., fire, smoke, security breaches, equipment status). They can operate in three modes:
    • NORMAL: For latching alarm devices (e.g., pull stations, smoke detectors). The transponder resets when the sensing device resets.
    • LATCH: For momentary alarm indications (e.g., door switches). The transponder latches in the alarm state until reset by the Central Control Console.
    • KEY: For both momentary and latching devices. The transponder latches in the alarm state until a keyswitch for that monitor point is momentarily activated, ensuring authorized personnel reset.
  • Control Points: These are output points that activate various building systems or devices in response to system events or operator commands (e.g., activating fire signals, shutting down HVAC, starting emergency generators).
  • Central Control Console: The main user interface, comprising a CPU, CRT (Cathode Ray Tube) for display, and a printer for logging events. It manages communication with transponders, processes alarms, and provides system status.
  • Annunciators: Peripheral devices that provide visual and/or audible indications of system status or alarms, often located in strategic areas of a building.

Important Technical Specifications

The system's technical specifications are primarily determined by jumper and switch settings, which configure communication baud rates, point statuses, and device addresses.

Transponder Configuration:

  • Channel Number: Identifies the communication channel for the transponder (e.g., 1-8).
  • Transponder Number: A unique identifier for each transponder.
  • Encoder Numbers and Addresses: Each encoder within a transponder has a number (e.g., 1-128) and a 4-bit binary address (00-15). The address is set by jumpers connecting to 12VDC (HIGH) or GND (LOW) for bits 1, 2, 4, and 8.
  • Monitor Point Status: Configured as Normally Open (NO) or Normally Closed (NC) via jumpers on the zone interface board.
  • Control Point Contacts: Configured as Normally Open (NO) or Normally Closed (NC) via jumpers on the zone interface board, determining whether the control circuit is opened or closed when the relay is energized/de-energized.
  • Transponder Baud Rate: Selectable via jumpers on the motherboard (37.5, 75, 150, or 300 baud). All transponders on a channel must operate at the same baud rate.

Central Control Console Configuration:

  • Channel & Annunciator Baud Rate: Configured via jumpers on the console motherboard. These can be set independently for each communication board.
    • 256 Console: Baud rates include 37.5, 75, 150, 300. Jumper locations are specified in a table (e.g., 1-8 for 37.5 baud annunciator, 2-8 for 37.5 baud channel).
    • 512 Console: Baud rates include 37.5, 75, 150, 300. Jumper locations are specified in a table (e.g., 1-7 for 37.5 baud annunciator, 3-7 for 37.5 baud channel).
  • Printer & CRT Baud Rate: Configured via jumpers on the console motherboard. The CRT uses the same baud rate as the printer.
    • 256 Console: Baud rates include 110, 150, 300, 1200, 4800. Jumper locations are specified in a table (e.g., 2-6 for 110 baud, 2-3 for 4800 baud). Earlier 256 versions used 1200 baud, while more recent 512 versions use 4800 baud.
    • 512 Console: Baud rates include 110, 150, 300, 1200, 4800. Jumper locations are specified in a table (e.g., 3-7 for 110 baud, 3-4 for 4800 baud).

CRT Switch Settings (on Logic PC Board):

  • S1-Position 3 (Baud Rate):
    • 1200 BAUD: Switch 1 OFF, 2 OFF, 3 OFF, 4 ON.
    • 4800 BAUD: Switch 1 ON, 2 ON, 3 OFF, 4 OFF.
  • S3 (General Settings):
    • Switch 1 ON, 2 ON, 3 ON, 4 OFF.
  • S4 (Full Duplex): Toggle switch in "UP" position.

Printer Switch Settings (Okidata CP110 and Centronics 730-3):

  • Okidata CP110:
    • Switch Package 4 (1200B / 4800B):
      • 1200B: Switch 1 ON, 2 OFF, 3 OFF, 4 OFF, 5 OFF, 6 OFF, 7 OFF, 8 OFF.
      • 4800B: Switch 1 ON, 2 ON, 3 OFF, 4 OFF, 5 OFF, 6 OFF, 7 OFF, 8 OFF.
    • Switch Package 12 (1200B / 4800B):
      • 1200B: Switch 1 OFF, 2 OFF, 3 OFF, 4 OFF, 5 OFF, 6 ON, 7 ON, 8 ON.
      • 4800B: Switch 1 OFF, 2 OFF, 3 OFF, 4 ON, 5 OFF, 6 ON, 7 ON, 8 ON.
    • Switch Package 9 (Self-Test Switches): All switches OFF for normal operation. SW #8 ON for print command, SW #7 OFF for entire character set print, SW #7 ON for selected character with switches 1-6 (ASCII code).
  • Centronics 730-3:
    • SW4 (256 Sys. 1200B / 512 Sys. 4800B):
      • 1200B (256 Sys.): Switch 1 OFF, 2 ON, 3 ON, 4 OFF, 5 ON, 6 OFF, 7 OFF, 8 OFF.
      • 4800B (512 Sys.): Switch 1 OFF, 2 ON, 3 ON, 4 OFF, 5 OFF, 6 OFF, 7 ON, 8 ON.
      • Other settings on SW4: DTR and REV. Channel, EVEN/ODD Parity, REV. Channel/INVERTED REV. Channel, NO Parity Check/Parity Check.
    • SW3 (Normal Operation / Self-Test Settings):
      • Normal Operation: Switch 1 OFF, 2 ON, 3 ON, 4 ON.
      • Self-Test Settings: Switch 1 OFF, 2 ON, 3 OFF, 4 OFF.
      • Other settings on SW3: Auto Line Feed Enable/Disable, Character Sets.

Usage Features

  • Flexible Configuration: The extensive use of jumpers and switches allows for highly customized system configurations to meet specific site requirements. This includes defining the behavior of individual monitor points (NORMAL, LATCH, KEY), the contact types for control points (NO/NC), and communication baud rates for various system components.
  • Scalability: The system supports different console types (256 pt. and 512 pt. Multiplex systems), indicating a degree of scalability for varying facility sizes and point counts.
  • Diagnostic Information: The Transponder Specification Sheet, shipped with each transponder, provides a comprehensive record of its configuration, which is essential for verification and troubleshooting.
  • Event Logging: The central control console's printer provides a hardcopy log of all system events, crucial for incident analysis and compliance.
  • Visual Interface: The CRT on the central control console offers a visual display of system status and events, enhancing operator awareness.

Maintenance Features

  • Jumper and Switch Documentation: The manual provides detailed diagrams and tables for all jumper and switch settings, making it straightforward to verify or modify configurations. This is critical for maintenance personnel to ensure the system operates according to specifications.
  • Electrical Hazard Warning: A prominent caution advises disconnecting electrical power before making any internal adjustments or repairs, emphasizing safety during maintenance.
  • Qualified Personnel Requirement: Installation and servicing are explicitly stated to be performed by qualified Simplex Representatives, ensuring proper handling and expertise.
  • Troubleshooting Aids: The information on jumper placement and switch settings serves as a fundamental troubleshooting tool, allowing technicians to quickly identify and correct misconfigurations.
  • Keyswitch for Monitor Points: The option to install a keyswitch for KEY operation on monitor points provides an additional layer of security, ensuring that alarms are reset only by authorized personnel, which is a key maintenance and operational control feature.
  • Transponder Specification Sheet: This document is vital for maintenance, as it contains the as-built configuration of each transponder, including channel, transponder, encoder numbers, addresses, and monitor/control point settings.

Simplex 2100 Specifications

General IconGeneral
BrandSimplex
Model2100
CategoryMultiplexer
LanguageEnglish