The first three switches on Sl set the terminal’s baud rate.
BAUD RATE
Sl-1 Sl-2
si-3
300 0 0
1
1200 0
1
0
2400
1
0
0
4800
1
0
1
9600
1 1 0
Note:
Refer to Figure 3 to determine switch positions for “1 s” and “0s”.
Switches 4 through 8 are set as indicated below. Factory switch settings are in bold.
SWITCH NO. SETTING
4 0
1
5
0
1
6 0
1
78
00
01
10
11
FUNCTION
Auto Scroll disabled
Auto scroll enabled
Auto line feed disabled
Auto line feed enabled
Half duplex
Full duplex
Odd parity
Even parity
Marking
Spacing
The switches on switch package S2 are set as below. Factory settings are in bold. Refer to Figure 4 to deter-
mine switch positons for “1 s” and “OS”.
SWITCH NO. SETTING
FUNCTION
1
2
3
4
576
7
8
0
Light characters displayed on dark
background.
1 Dark characters displayed on light
background.
0 Parity check disabled.
1 Parity check enabled.
0
60 Hz operation
1
50 Hz operation
**NOT USED**
00
U.S. character set
01
Belgium/France/Azerty
10
Germany/Switzerland
11
U.K./Selectric
0
Steady cursor
1
Blinking Cursor
0
Cursor is a rectangular block.
1 Cursor is an underline.
IMPORTANT: The terminal reads switch settings at power-up. If you change a setting you must turn the terminal
OFF and then ON again for the change to take effect.
Connect the ADDS Viewpoint terminal to the BMUX as indicated in Figure 5.