2. To display the current Setup Menu on your screen, press CTRL-TAB twice.
l
The current Setup Menu is now displayed on your screen with a blinking cursor positioned at the first field
-Terminal mode. Now you must match the parameters shown in Figure 7.
3. Using SHIFT-Cursor Up or SHIFT-Cursor Down arrow keys, position the cursor at the desired field to be
changed.
Note: Use CTRL-SHIFT-Cursor Up or Cursor Down arrow keys to change screen contrast.
SETUP MENU
1 Terminal mode
4 Baud rate
0 Parity
N Display parity error
Y Full duplex
Y Auto scroll
N Auto line feed
N Light background
N Underline cursor
N Blinking cursor
N Keyclick
N Bell on 73rd column
N 50 Hz operation
0 Language
N Keycap option
N Disable CTRL-2 (3A/3A + only)
N Space advance (3A only)
N Programmable function keys
MODES
0 = Al
1 = A2
2 = 3A
3=3A+
BAUD RATES
0= 110
l= 150
2 = 309
3 = 600
4 = 1200
5 = 1800
6 = 2400
7 = 4800
8 = 9600
9 = 19200
PARITY
0 = Odd
1 = Even
2 = Marking
3 = Spacing
LANGUAGE SELECTION
0 = United States
1 = France
2 = Germany/Switzerland
3 = Sweden/Finland
4 = Denmark/Norway
5 = Spain/Portugal
6 = United Kingdom
l
Cursor UP & DOWN for selection
l
Enter parameter changes
l
HOME saves changes and exits
l
ESC exit without saving changes
l
CTRL-UP & DOWN changes contrast
ADDS Basic+ Setup Menu -
2120 Multiplex Operating Parameters
FIGURE 7
4. Enter Y (yes), N (no), or the appropriate numeric value to match parameters given in Figure 7.
Note: The CTRL key functions listed on page 3 can only be used in the A2 terminal mode.
5. To store new parameters and exit Setup Menu, press SHIFT-HOME keys simultaneously, then release.
Note: a. To restore previous parameters and exit Setup Menu, press the ESC key.
b. To restore default parameters to Setup Menu, press SHIFT-ESC keys simultaneously, then release.
l
DEFAULT PARAMETERS LOADED is displayed at the bottom of your screen. Press CTRL-TAB twice
to see the default values displayed in your Setup Menu.
Connect ADDS Basic + to the BMUX as shown in Figure 5.