Simplex IDNet 4009 - Mounting the 4009 IDNet Unit

Simplex IDNet 4009
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
Note: T
he following pages provide a detailed description of the installation.
If you experience problems that cannot be resolved, call your local
Simplex Branch Office.
Use the following procedure when mounting a 4009 IDNet.
CAUTION: Read all instructions carefully before cutting conduit/service
entrances and installing back box. Failure to comply with all
installation requirements may result in a violation of UL or
FCC regulations.
1. Carefully open the shipping container.
2.
Remove the 4009 IDNet from the shipping container and lay the unit on
a
f
lat surf
ace.
3.
Unlock and open the panel door. Remove the electronic card cage assembly
and store it in a safe dry area. Disconnect the AC wiring harness from th
e
card cag
e before removing it from the box
.
4
. Determine the amount and proper location of conduit/service entrances (s
ee
Fig
ure 6). Make all appropriate entrances into the back box
.
P
ower-Limited and Non-Power Limited wiring must enter through separate
conduit/service entrances. AC power entrance into the back box
is
recom
mended at the bottom right side of the back box
.
Maximum intrusion into back box for conduit is ½ -inch.
Figure 6. Installing the 4009 IDNet Back Box
Continued on next page
System Installation, Continued
Mounting the 4009 IDNet
BATTERY
MOUNTING
AREA (NO
CONDUIT
ENTRY)
KNOCKOUT
SCREW/NAIL
HOLES for SEMI-
FLUSH
MOUNTING
TOP VIEW
NON-POWER-LIMITED
WIRING ONLY
C
B
D
E
A
Recommended Conduit Locations
Locate conduit entry approximately
where shown.
A. Cl
ass B or Class A Fiber Feed and
AC
Power
B. Notification Appliance Circuits
and
I
DNet
C. Class A Fiber Return
D. Notification Appliance Circuits
and
I
DNet or Class A Fiber Return
E. Co
ntrol Inputs: IDNet or
Notification Appliance Circuits