Compatible Controller
Data Sheet
Reference
Controller
Output
IDNAC SLC
Output Voltage
Appliance Voltage
Design Reference
4100ES with EPS+ or EPS Power Supply S4100-0100
IDNAC SLC
29 VRMS
(regulated)
23 VRMS
(with 6 VRMS drop)
4009 IDNAC Repeater S4009-0004
Common Specifications (see page 2 for appliance dimensions)
Environmental 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C)
Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm
2
to 3.31 mm
2
); two wires per terminal for in/out wiring
Installation Instruction
Reference
Clear/Amber Strobes 579-847
Adapter Skirts 574-790
Adapter Plate 574-791
Strobe Specifications
Typical Operating Voltage Range
23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS rating)
Supervisory Requirements 1 unit load each, 2 unit loads total per 4906-9208
Flash Rate and Synchronized SLC Loading
1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum 30
resistance between appliances
Candela Setting 15 cd 30 cd 75 cd 110 cd
23 VRMS Current Ratings, for connection to
IDNAC Addressable SLCs
50 mA 75 mA 137 mA 190 mA
Note: Amber strobes and clear strobes provide notification for two different functions and are not activated at the same time.
Compatible Controller
Data Sheet
Reference
Controller Output
Available Strobe
Intensity
Appliance Voltage
Minimum
4100ES or 4100U with TrueAlert Power Supply S4100-0031
TrueAlert
Addressable SLC
15, 30, 75, and
110 cd
17
VRMS 4009 TPS, Remote TrueAlert Power Supply S4100-0037
TrueAlert Addressable Controller (4009T) S4009-0003
Electrical Ratings Difference for Retrofit Applications
Voltage Range 17 VRMS to 31 VRMS, Special Application
Candela Setting 15 cd 30 cd 75 cd 110 cd
17 VRMS Current Ratings, use when connected
to TrueAlert Addressable SLCs per above
64 mA 98 mA 187 mA 253 mA
TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference
Specifications