DC INVERTER U-MATCH AIR CONDITION MAINTENANCE
159
8. Mount a new
compressor and fix it
onto the compressor
support
Put the new
compressor to correct
position.
Use spanner to
tighten the bolts fixing
the compressor.
Do not put the
compressor upside
down during
installation.
9. Connect the suction
and discharge pipe of
compressor to system
pipeline
Use gas welding to
heat the suction and
discharge pipes. Then,
pull them out from the
compressor.
Weld by charging
nitrogen for protection,
with the nitrogen
pressure kept at
0.5±0.1kgf/c 󱚸(relative
pressure).
During heating, take
care to prevent the
substances around
from burn due to high
temperature.
10 Mount the gas-liquid
separator and fix it
Put the gas-liquid
separator to correct
position.
Use spanner to
tighten the nuts fixing
the gas-liquid
separator and
compressor support.