DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
has to endure the unnecessary outside force. (As shown in Figure 1-3-10)
Drain hose(attachment)
Below75mm
Below500mm
Figure 1-3-10
Please install the drain hose according to the following process if several drain hoses join together.
(As shown in Figure 1-3-11)
T-tie in join drain hose
Above100mm
The specs of the selected join drain hose should fits the running capacity of the unit.
Figure 1-3-11
Check the smoothness of drain after installation.
Check the drain state by immiting 600cc water slowly from the outlet vent or test hole. (As shown in
Figure 1-3-12)
Check the drain in the state of refrigerating after installation of the electric circuit.
Test hole cover
Drain hose
< Immiting water from the rest hole>

Drain vent for repair use (plastic
stopper is included) (drain the water
in waterspout by this outlet vent)
[Way of immiting]
Test hole
<Immiting water from the outlet
vent terminal>
Plastic water pot (The length of the
pipe should be about 100mm.)
Figure 1-3-12