DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.3.7 Installation of panel
1
Set the panel to the indoor unit body by matching the position of the swing flap motor
of the decoration panel to the piping position of the panel to the piping position of the
indoor unit as shown in Figure 1-3-13.
Figure 1-3-13
Hang the latch, which is located on the opposite side of the swing flap motor on the panel,
temporarily to the book of the indoor unit. (2 Positions)
Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit.(Be careful not
to let the swing motor lead wire get caught in the sealing material.)
Screw all 4 hexagon head screws located right beneath the latches in approximately 15mm.(Panel
will rise)
Adjust the panel by turning it to the arrowed direction in Fig.4 so that the ceiling opening is
completely covered.
Tighten the screws until the thickness of the sealing material between the panel and the indoor unit
body is reduced to 5~8 mm.
2 Precautions:
Improper screwing of the screws may cause the troubles shown in Figure 1-3-14.