If a leak is suspected, all naked flames shall be removed / extinguished. If a
leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the
system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged
through the system both before and during the brazing process.
2.2.5 Refrigerant Adding
NOTE!
Before and during operation, use an appropriate refrigerant leak detector to
monitor the operation area and make sure the technicians can be well aware of
any potential or actual leakage of inflammable gas. Make sure the leak detecting
device is applicable to inflammable refrigerant. For example, it should be free of
sparks, completely sealed and safe in nature.
See the fol
lowing table for the amount of additional refrigerant.
Item
Model
Standard
Pipe Length
Unnecessary
Charge Pipe
Length
Additional
Refrigerant Amount
for Extra Pipe
ASGE-12BI2
5.0m
≤7.0m
16
g/m
ASGE-18BI2
ASGE-24BI2
20
g/m
ASGE-36BI2
ASGE-36BI2-3
ASGE-42BI2
ASGE-42BI2-3
7.5m
≤
9
.
5
m
35
g/m
ASGE-48BI2-3
2.2.6 Installation of Drain Pipe
(1) It is not allowed to connect the condensate drain pipe into waste pipe or
other pipelines which are likely to produce corrosive or peculiar smell to
prevent the smell from entering indoors or corrupt the unit.
(2) It is not allowed to connect the condensate drain pipe into rain pipe to
prevent rain water from pouring in and cause property loss or personal
injury.