DC INVERTER U-MATCH AIR CONDITION                                       MAINTENANCE 
 
106
◆Malfunction display: E1 Compressor High Pressure Protection 
Mainly check the inlet and outlet of main pipe connecting with 
each indoor unit and capillary of indoor and outdoor units. 
Replace the parts like filter, capillary and so on.
Check if indoor unit fan and outdoor unit fan 
run
Check if swing louver of indoor unit is 
completely open
High pressure switch
Y
N
Check if the pressure is really high pressure 
with the measurement of a manometer
Check if pressure switch is 
normal
Replace the main board 
of the outdoor unit.
Replace pressure 
switch
Check if operation mode of indoor 
unit is properly set
N
N
Y
Y
Y
Y
Check if gas valve and liquid valve 
are completely open
Refer to Instruction 
Manual of indoor unit
Check if the panel of outdoor unit is 
firmly closed?
N
N
Completely open the 
valve
Close the panel
Check if the air return and supply from heat exchanger 
of indoor unit and outdoor unit are smooth
Remove the blockage
Measure the fan motor and 
signal input
Measure swing motor 
and signal input
N
N
N
System pipeline is blocked
Y
Y
Y
Y
Check if there is filth blockage to indoor/
outdoor filter or heat exchange fin
Refer to Care and 
Maintenance