2.4 Communication malfunction 
Detection of the quantity
 of installed indoor units: 
After 3min of energizing, if the outdoor unit does not receive the communication data 
of certain indoor unit, the outdoor unit wi
udge that indoor unit is not installed and will treat it as it is not installed. If the outdoor unit receives the communication data of
 
that indoor unit later, the outdoor unit 
will treat that unit as it is installed. 
2.5 Overcurrent Protection 
a. Overcurrent protection of complete unit; b. phase 
wire current protection; c. compressor phase current protection
2.6 Compressor high-pressure protection 
2.6.1 
When the high-pressure switch is detected cut off for 3s continuously, the compressor will enter high-pressure protection
it stops when reaching set temperature. Meanwhile, the outdoor unit will send the signal of “high-pressure protection” to th
 
After the appearance of high-pressure protection, when the high-pressure switch is detected closed for 6s continuously
, 
the compressor can resume running only after cutting off the po
wer and then putting through the power. 
2.7 Compressor overload protection 
If the compressor overload switch is detected having movement, the indoor unit 
will display the corresponding malfunction as it
when  the  indoor  temperature  reaching  set  temperature.  When  the  compressor  stops  for  more  than  3min  and 
switch is reset, the unit will resume operation status automatically. If the protection appears for more th
an 
6 times (if the running time of the compressor is longer than 30min, the protection times record 
will be cleared), the unit can
operation status  automatically, but can resume running only after  cutting off the power and then putting  through 
wer. 
2.8 Compressor Phase-lacking Protection 
When 
the compressor starts, if one of the three phases is detected open, the compressor will enter phase-lacking 
malfunction will be cleared after 1min, the unit will restart and then detect if there is still has phase-lacking protectio
protection is detected for 6 times continuously, the compressor will not restart but can resume running only afte
off  the  power  and  then  putting  through  the  power.  If  the  running  time  of  the  compressor  is  longer  than  7min, 
the 
protection times record 
will be cleared. 
When the IPM module protection is detected, the unit will stop as the indoor temperature reaching set temperature, PFC is
display  IPM  protection  malfunction.  After  the  compressor  stops  for  3min,  the  unit  will  resume  operation  status
if the IPM  protection  is detected for more  than  6  times continuously (If  the  running  time of the compressor  is
than 7min, the protection times record will be cleared), the system will stop and send the signal of module protection t
The unit can not resume operation status automatically, but can resume running only after cutting off the power an
d 
then putting through the po
wer. 
2.9.2 IPM module overheating protection
 
T
IPM
η85ć, prohibit to raise frequency; 
When  T
IPM
≥90ć,  the  operation  frequency  of  compressor  lows  down  by  15%  every  90s  according  to  the 
 requirement of the complete unit. It will keep 90s after lowing down the frequency. After lowing down the frequency, i
IPM
≥90ć, the unit will circulate the above movement until reaching the minimum frequency; if 85ćζT
IPM
ζ90ć, the unit will
when T
IPM
≤85ć, the unit will run at the frequency according to the capacity requirement; 
When T
IPM
≥95ć, the compressor stops. After the compressor stops for 3min, if T
IPM
ζ85ć, the compressor and 
will resume operation.