Specifications 11
Sale Model
SDV4-140EAA
SDV4-160EAA
Code
220095102340
220095102370
Dimension(W x H x D)
mm
900 x 1327 x 320
900 x 1327 x 320
Outdoor Unit
Packing (W x H x D)
mm
1030 x 1456 x 435
1030 x 1456 x 435
Net/Gross weight
kg
95/103
102/113
Type
R410A
R410A
Refrigerant
Charged volume
g
3900
3900
Throttle type
Electronic
expansion valve
Design pressure
MPa
4.4/2.6
4.4/2.6
Liquid side/ Gas side
mm
Ф9.52/Ф15.9
Ф9.5219.1
piping
Refrigerant
Max. refrigerant pipe length
m
100
100
Max. difference in level
m
8
8
Connection
Power wiring
mm
2
5 core x 2.5
wiring
Signal wiring
mm
2
3 core shielded wire x 0.75
Cooling -1548
Cooling -1548
Ambient temp
Heating -1527
Heating -1527
Notes:
1. The cooling conditions: indoor temp.: 27DB (80.6), 19WB (60) outdoor temp.: 35DB (95) equivalent pipe length:
5m drop length: 0m.
2. The heating conditions: indoor temp.: 20DB (68), 15WB (44.6) outdoor temp.: 7DB (42.8) equivalent pipe length:
5m drop length: 0m.
3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of *m(0.9m for
80model, 1m for 105 model,1.2m for 120~180 model). During actual operation, these values are normally somewhat higher as a
result of ambient conditions.
4. The aboved datas may be changed without notice for future improvement on quality and performance.