60 Electric System
4) The wiring with different voltage should not pass through the same wire tube.
5) Total sectional area of wiring through wire tube shall not exceed 40% valid area of stuffing tube.
6) Fixing point of wire tube support shall follow the standard below:
Normal diameter of wire tube
Largest gap between fixed points of wire tube
Mm
Metal pipe
Plastic pipe
15~20
1.5m
1m
25~32
2m
1.5m
40~50
2.5m
2m
5
.
4 Outdoor unit power wiring selection
1) Separate Power Supply without power facility.
The shortest wiring
diameter
(mm)
Manual switch (A)
Creepage
protector
≤20m
≤50m
GND
Capacity
Fuse
Model
Power
S
D
V
4
14kW
380~415V
/
3N
/50Hz
4*3.3
4*4.0
4.0
30
25A
<100mA,0.1sec
16kW
380~415V
/
3N
/
50Hz
4*3.3
4*4.0
4.0
30
25A
<100mA,0.1sec
Note:
The length in the table equals the value of power cord connecting outdoor units, indicating the condition
that the voltage dropping range is within 2%. If the length exceeds the above figure, please
select the wire
diameter according to relevant standard.
2) With power facilities.