Troubleshooting 69
1. PCB ports instructions
PCB ports instruction
Inspection port for inverter module voltage
Mutual inductor for compressor DC current
Activation port of inverter module
The left the first pin:DC
3.3V
The left the first pin:DC
310V,the third pin:DC 15V
The left the first pin:DC
310V,the third pin:DC 15V
Loading output terminal(4-way valve control)
The left the first pin:DC 12V
Input current of the mutual inductor at the inverter compressor
SW3 net address code automatically
13CN11
Internet group control of indoor units
DC 2.5-2.7V
14CN10
Communication between indoor and outdoor units
DC 2.5-2.7V
15CN9
Inspection port for outdoor ambient temp. and condenser
coil temp.
DC 0-5V
16CN8
Air discharge temp. sensed port at the compressor
DC 0-5V
17CN6
Input port for system pressure inspection
DC 0-5V
18CN250
Input port for power supply of the main control board
AC 220V
19CN64
Loading output terminal(18kW: solenoid valve SV5 control; reserved for 14kW)
AC 220V
20CN62
Loading output terminal
(delay control of DC power)
AC 220V
21CN60
Loading output terminal(crankcase heating control)
AC 220V
22CN58
Loading output terminal(4-way valve control)
AC 220V
23CN56
Loading output terminal(solenoid valve SV6 control)
AC 220V
24CN67
Reserved
----
25CN65
Loading output terminal(16kW: solenoid valve SV5 control; reserved for 14kW)
AC 220V