STARTING UP
If a replacement AVR has been fitted, or the re-setting of the voltage adjustment is required, please
proceed as follows:
1. Connect the wires coming from the alternator according to the description in the
CONNECTION DIAGRAM and the type of alternator to be used.
2. Check that the DIP switches group 2 and group 1 are consistent with the characteristics of
the machine (voltage, frequency, remote control)
3. Before running alternator, turn the volts trimmer “V” anti-clockwise
4. Turn stability trimmer “ST” to midway position
5. Start alternator set, and run on no load at nominal frequency e.g. 50-53 Hz or 60-63 Hz
6. Carefully turn volts trimmer “V” (or external pot, if fitted) clockwise until rated voltage is
reached
7. If instability is present at rated voltage, refer to stability adjustment, and then re-adjust voltage
if necessary