6 Troubleshooting
SMA Solar Technology AG
User ManualSTP33-62-US-41-BA-en-1154
Event number Message, cause and corrective measures
8003
Active power limit Temperature
The inverter has reduced its power output for more than 10 minutes due to ex-
cessive temperature.
Corrective measures:
Clean the cooling fins on the rear of the enclosure and the air ducts on
the top using a soft brush.
Ensure that the inverter has sufficient ventilation.
Ensure that the ambient temperature +35°C (95°F) has not been
exceeded.
Ensure that the inverter is not exposed to direct solar irradiation.
8101
8102
8103
8104
Communication failure
The cause must be determined by the Service.
Corrective measures:
Contact the Service.
8208
Self-test for arc fault detection: interference level too high
An error has occurred during the self-test of the arc-fault circuit interrupter. The
cause must be determined by the Service.
Corrective measures:
Contact the Service.
8209
Self-test for arc fault detection: interference level too low
An error has occurred during the self-test of the arc-fault circuit interrupter. The
cause must be determined by the Service.
Corrective measures:
Contact the Service.
9002
SMA Grid Guard code invalid
The SMAGridGuard code entered is incorrect. The operating parameters are
still protected and cannot be changed.
Corrective measures:
Enter the correct SMAGridGuard code.