5 Troubleshooting SMA America, LLC
22 SB30-40-BA-eng-BUS121010 User Manual
Goes out briefly
once per second
Derating
At temperatures above +113°F (+45°C), the
inverter continues to operate but reduces the
power so as to protect the internal
components from overheating.
Corrective measures:
Ensure that the inverter has sufficient
ventilation.
Ensure that air is emerging from the fan
enclosure. If no air is emerging from the
fan enclosure, clean the fan enclosure
(see section 6.4).
B Red LED Glowing Grounding fuse tripped
The grounding fuse has been tripped or is
missing. The grounding fuse protects the PV
plant if a ground fault is present in the PV
array.
Corrective measures:
Contact installer.
C Yellow LED Glowing Control system error
The inverter is no longer feeding into the
power distribution grid.
Corrective measures:
Contact installer.
Blinking AFCI self-test
The inverter is performing an AFCI self-test.
Glows for 5 s,
goes out for 3 s,
blinks twice
Grid failure
The power distribution grid has failed or the
AC miniature circuit-breaker has been
triggered.
Corrective measures:
Ensure that there is no power distribution
grid failure.
If there is no power distribution grid
failure, contact the installer.
Position Description Status Explanation