11 Operating Data and Parameters
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-58130
Name Description Value/range Explanation Default
value
P-WSubValRun Substitute value for ac-
tive power limitation in
normal feed-in operation
during communication
disturbance
0kW to 550kW SunnyCentral500CPXT 550kW
0kW to 700kW SunnyCentral630CPXT 700kW
0kW to 792kW SunnyCentral720CPXT 792kW
0kW to 836kW SunnyCentral760CPXT 836kW
0kW to 880kW SunnyCentral800CPXT 880kW
0kW to 935kW SunnyCentral850CPXT 935kW
0kW to 990kW SunnyCentral900CPXT 990kW
0kW to 1100kW SunnyCentral1000CPXT 1,100kW
Q-VArSubVal Substitute value for reac-
tive power setpoint out-
side of normal feed-in
operation during commu-
nication disturbance
−245kVAr to
+245kVAr
SunnyCentral500CPXT 0kVAr
−310kVAr to
+310kVAr
SunnyCentral630CPXT
−346kVAr to
+346kVAr
SunnyCentral720CPXT
−365kVAr to
+365kVAr
SunnyCentral760CPXT
−385kVAr to
+385kVAr
SunnyCentral800CPXT
−409kVAr to
+409kVAr
SunnyCentral850CPXT
−433kVAr to
+433kVAr
SunnyCentral900CPXT
−485kVAr to
+485kVAr
SunnyCentral1000CPXT
PF-PFSubVal Substitute value for cosφ
outside of normal feed-in
operation during commu-
nication disturbance
The lower limit is defined
by the parameter PFAb-
sMin.
0.5 … 1 1
PF-PFExtSubVal Substitute value for exci-
tation type during com-
munication disturbance
OvExt Overexcited OvExt
UnExt Underexcited