EasyManua.ls Logo

Smiths Kiosk - Commissioning - Kiosk and Trafalgar

Default Icon
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Issue 002 - October 2018 | SmithsEP.co.uk | 7
8. Secure product to the oor
9. Commissioning
Align the TRV head over the valve body with
the indicator point at setting V. Ensure that the
TRV head is square to the body, screw the TRV
head onto the body in a clockwise direction
until tight, being careful not to over – tighten
the head on the body
Turn on the heating system
Fully open Thermostatic Radiator Valve (in the
system ow) to Setting V while leaving the Lock
Shield Valve (in the system return) totally closed
Allow the system to ll the heat emitter
Open the air vent situated on the heat
exchanger
Once the heat emitter is free of air, close
the air vent
Open Lock Shield Valve and allow the heating
system to run for minimum of 1 hour
After minimum 1-hour period, the heating
system may require further bleeding.
Follow best practices when purging the heating
system of air
Note: It may be necessary to balance the heating
system to achieve best ow and/or water
temperature.
10. Re-t casing
6. Prepare ow/return connection
and connect to heating system
using suitable ttings
Pipe connection is 15mm
Flow connection should be TRV End
Isolating valves must be tted to ow and
return pipework for servicing
7. Ret end panels
Commissioning
All factory tted connections/compression joints
should be inspected prior to lling the system, in
case of loosening during transit