TAKEDO - 3VF HYDROVERT NXP USER MANUAL Version 05 dated 10-08-2017
TABLE 2 – Current, dimensions and weight
4 – CONNECTION OF THE POWER CIRCUIT
L1;L2;L3 Network power supply input
Connect the power supply network input phases, independently
of the cyclic direction.
Connect the three output phases to the contactors and therefore
to the motor
External braking resistance
Connect the external braking resistances (if necessary)
Connect to the system earth
For the dimensioning of the cables and the position of the terminals, refer to the “POWER CONNECTIONS”
chapter in the original VACON INSTALLATION AND MAINTENANCE TECHNICAL MANUAL (VACON NXP
series inverter) available at www.it.vacon.com.
INVERTER NXP 400 VOLT SERIES (380÷500V)
CODE
FUSES
gG/gL
(A)
BRAKING RESISTANCE (eventual (**))
SUPPLIED BY SMS
MINIMUM
)
DIMENSIONS
LxDxH (mm)
HVP00185 25
N°1 x 50Ω 1500W 42Ω
445x110x140
HVP00315 35
N°1 x 50Ω 1500W 42Ω
445x110x140
HVP00365 63
N°2 x 50Ω 1500W
HVP00455 63
N°2 x 50Ω 1500W 21Ω
445x110x140 (*)
HVP00615 63
N°3 x 50Ω 1500W 14Ω
445x110x140 (*)
HVP00725 80
N°4 x 50Ω 1500W 6.5Ω
445x110x140 (*)
HVP00875 100
N°5 x 50Ω 1500W
6.5Ω
445x110x140 (*)
HVP01055 125
N°7 x 50Ω 1500W 6.5Ω
445x110x140 (*)
HVP01405 160
N°7 x 50Ω 1500W 3.3Ω
445x110x140 (*)
HVP01685 200
N°12 x 50Ω 1500W
3.3Ω
445x110x140 (*)
(**) The braking resistance is necessary only if HYDROVERT is used to control the downward run.
(*) The total dimension is that indicated multiplied by the number of resistances.
TABLE 3 – Fuses and braking resistances for 400V power supply voltage