LEDs and push buttons
Launch Bluetooth pairing process
Start auto-discovery and auto-addressing of slave devices
USB port for conguration
Not used
ALARM
ON
COM
ADDR.
ETHETH
EXT.
DIRIS M-xx
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
LED OFF Stable Flashing
ON
(Green)
Device is off Product ON
- 10 sec During
startup
- Manual blinking
command
ALARM
(Red)
No active alarm
Measurement
alarm active on a
slave device
System alarm
active on a
device
COM
(Orange)
No
communication
-
Product
communicating
(Blue)
Bluetooth is
deactivated
Bluetooth is
activated
Ongoing
Bluetooth pairing
process
®
®
5
Communication architectures
*
24 VDC
(20 W max)
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ALARM
ON
COM
DIRIS M-xx
DIRIS Digiware M-50/M-70
Digiware Bus
Ethernet
120 Ω
NC
RS485 Digiware
LIYCY-CY
Ethernet
Digiware
Bus
MASTER
24 VDC
(20 W max)
Ethernet
24 V
SUPPLY
*
24 VDC
(20 W max)
RS485
DIRIS Digiware M-50/M-70
DIRIS B
Digiware Bus
120 Ω
NC
RS485 Digiware
LIYCY-CY
Ethernet
Digiware
Bus
SLAVE
24 VDC
(20 W max)
Ethernet
24 V
SUPPLY
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ALARM
ON
COM
DIRIS M-xx
a. RS485 Master
b. RS485 Slave
* If the 24 VDC power supply is not provided by Socomec, a 1 A / 24 VDC fuse must be used. For North America, the use of recognized fuses is mandatory.
4
Conguration via Easy Cong software
DIRIS Digiware
M-xx
DIRIS B
RS485
Digiware Bus
Digiware system
Easy Config
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ALARM
ON
COM
DIRIS M-xx
Ethernet
DIRIS Digiware
M-xx
DIRIS B
RS485
Digiware Bus
Digiware system
Easy Config
ETHETH
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLYRS485
NC
ALARM
ON
COM
DIRIS M-xx
USB
Ethernet USB
3
System wiring
DIRIS
DigiwareU
Voltage
Inputs (U)
DIRIS
DigiwareI
Current
Inputs (3I)
Digiware Bus
Com
Ethernet
RJ45
U
Voltage inputs
50-300VAC PH/N
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
4 positions
screw 0.25 Nm max.
L1
L2
L3
N
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
2 positions - screw 0.25 Nm max.
Supply
24VDC SELV
(**)
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
3 positions - screw 0.25 Nm max.
Com
RS485 Modbus
I
Current
inputs
Sensors 3x
Micro
USB
type B
(*)
Only use a SOCOMEC Digiware bus cable
(UTP RJ45 straight, twisted pair, unshielded,
AWG24, 600V CAT V -10 ... +70°C).
When wiring, make sure you separate the
low voltage (LV) section and the very low
voltage (SELV) section to prevent any risk of
electric shock.
Maximum 1200 m for RS485 bus
Max. length for Digiware bus = 300 m
(witha maximum of 2 C-32 repeaters)
(*) Functional Earth
(**) SELV = Saftety Extra Low Voltage
When installed close to uninsulated live parts, use
personal protective equipment to manipulate the device